Opti-UPS smart protocol
This is a partial decoding of the protocol used in the Opti-UPS PowerES
models. There are a bunch of things missing, and the UPS itself is
very difficult to probe due to an annoying 20 second pause every time
a command is sent.
| Command |
Apparent meaning |
Typical value |
| AG |
UPS Status |
This field is in hex, but it's bitmapped.
- bit 3: 1 = overload
- bit 4: 1 = replace battery
- bit 5: 1 = on battery, 0 = on line
- bit 6: 1 = low battery
|
| Test group |
| TR |
Test results |
- 00 = Unknown
- 01 = Passed
- 02 = Warning
- 03 = Error
- 04 = Aborted
- 05 = In Progress
- 06 = No test init
|
| Battery group |
| BT |
Battery temperature (deg C) |
0033 |
| BV |
Battery voltage (.1 volts) |
0140 |
| Configuration group |
| FA |
Output VA |
0280 |
| FF |
Input frequency (.1 Hz units) |
600 |
| FH |
High transfer point |
144 |
| FL |
Low transfer point |
093 |
| FO |
Output volts |
120 |
| FP |
Output power |
0280 |
| FR |
Output frequency (.1 Hz units) |
600 |
| FT |
Transfer point? |
121 |
| FV |
Input voltage |
120 |
| Input group |
| IM |
Manufacturer |
OPTI-UPS |
| IO |
Model |
280es |
| IS |
Firmware version |
V1.5B2 (change this and their software stops working) |
| IZ |
Serial number |
801292607978 |
| Input group |
| NF |
Input frequency (.1 Hz) |
605 |
| NV |
Input voltage |
114 |
| Output group |
| OF |
Output frequency (.1 Hz) |
605 |
| OL |
Output load |
75 |
| OV |
Output volts |
120 |
Cable information
According to contributor Stephen S., the stock PnP cable that is provided
with the unit does not work properly with Linux. Cables using this pinout
should perform better.
- UPS 6 - PC 3
- UPS 9 - PC 2
- UPS 4 - PC 5
UPS end = male, PC end = female.
No more updates
I no longer have access to this hardware, so this page will probably
remain frozen in this state forever. The 20 second delay was unbelievably
annoying, so this turn of events is not entirely bad. If you can circumvent
this problem and want to continue the page, then contact me.
|